INSTALLATION COMFORT AIR CURTAIN
en-14
en
2.5.1 Particulars
Caution:
c The central heating system’s supply and return pipes
must be attached to the correct connectors 1. The
directions are indicated on the unit using arrows.
Keep the connectors 1 in place by using pliers when con-
necting the pipes.
Biddle recommends inserting a valve and a bleed on both
pipes close to the unit.
Application limitations for units with water heating
2.5.2 Frost protection
Take the following precautions if you install the unit in a room
where frost may occur:
Provide for constant circulation of the water at the right
temperature;
Add up to 20% glycol to the water when the unit is not in
operation during the wintertime;
Or bleed the system and the unit.
2.5.3 Connecting the water-side control
1. Open the unit.
2. Connect the unit and the three-way valve to the central
heating system as shown in the diagram.
Note:
n The diameter of the bypass pipe from Connection B
to the return pipe must be at least 22 mm.
Heating medium water with max. 20% glycol
Max. water supply
temperature
DF S-W, M-W: 90 °C
DF L-W: 70 °C
Max. air discharge
temperature
DF S-W, M-W: 70 °C
DF L-W: 45 °C
Max. operating pres-
sure
8bar